FIRE FIGHTING

SCF830-D-U

DISCONTINUED
EN12845 Diesel Fire pump Controller

Controllers for Diesel Fire Pumps according to EN 12845 and UNE 23500

SCF830-D-U are designed to meet and exceed the requirements of the EN 12845 and UNE 23500 standard; They are high specification instruments that apply the most advanced technology. They offer unrivalled features such as communications,  configurations, versatility and robustness.

SCF830-D-U controllers govern the starting and stopping process of the Diesel Fire Pumps and protect them through the action of the alarms both connected and generated by the controller itself; they visualise the most relevant values and information, also manage the communication with the operator and with both the contour elements and the remote manned centre

MAIN FEATURES: SCF830-D-U

Diesel Fire Pumps controllers: EN 12845 and UNE 23500

  • STANDARDS & TECHNICAL RULES
    1 Standard EN 12845 Ed.2016
    2 Standard UNE 23500 Ed.2021 & Ed. 2012
    3 Standard UNI 10779 Ed. 2014
    4 Standard IEC 61439-1 Ed. 2011 Low-voltage switchgear and controlgear assemblies
  • RANGE OF PRODUCTS (according to the type plate)
    1 Nominal supply voltage 230 Vac
    2 Nominal frequency 50Hz / 60Hz.

     

    RANGE OF PANELS ACCORDING TO BATTERY CHARGERS SCF830-D-U 12070 SCF830-D-U 12100 SCF830-D-U 24035 SCF830-D-U 24050
    Nominal Voltage 12 Vdc 12 Vdc 24 Vdc 24 Vdc
    Rated Amp 7 A 10 A 3,5 A 5 A
    DIN Power 96,6 W 138,0W 96,6 W 138,0 W
    Capacity of the batteries (C10) 200 Ah 285 Ah 100 Ah 142 Ah
  • CONSTRUCTIVE FEATURES
    1 Enclosure Ingress protection rating: IP65
    2 Protection against impacts degree: IK10 except PLC SAF830-D-U
    3 Fireproof degree: The fire is extinguished in <30s with dripping
    4 Display Graphic / Transflective
    5 Cabling Free of halogens
    6 Fire resistance: RZ1 according to EN50200 (Max: 830º / 90min)
    7 Working temperatures From -5ºC to 50ºC
  • MEASURING INSTRUMENTS IN THE DISPLAY
    1 Batteries 2 Voltmeter: Battery voltage
    2 2 Ammeter: Battery charging Amp
    4 1 Battery equalization timer
    5 Engine 1 Fuel tank level meter
    6 1 Oil pressure gauge (sensor not included)
    7 1 Engine wáter  thermometer (sensor not included)
    8 1 Engine oil thermometer (sensor not included)
    9 1 Engine speed meter (sensor not included)
    10 System 1 System pressure meter (sensor not included)
    11 1 Flow meter ( manual introduction / 4⁄20mA sender not included)
    12 1 Voltmenter AC V supply voltaje
  • PUMP & SYSTEM PROTECTION
    1 MAINS FAILURE
    2 OVER SPEED
    3 LOW OIL PRESSURE
    4 COOLANT HIGH TEMPERATURE
    5 LOW FUEL LEVEL
    6 LOW BATTERY A VOLTAGE
    7 LOW BATTERY B VOLTAGE
    8 CHARGER A FAULT
    9 CHARGER B FAULT
    10 HEATER PROTECTION TRIPPED
    11 CRANK ENGINE VOLTAGE FAIL
    12 FAILED TO START
    13 LOW DISCHARGE PRESSURE
    14 LOW RESERVOIR TANK
    15 LOW PRIMING TANK
    16 SPEED SIGNAL FAULT
    17 PRESSURE SWITCH SHORT-CIRCUIT
    18 PRESSURE SWITCH OPEN-CIRCUIT
    19 MAINS FREQUENCY FAIL
    20 COMMUNICATION
    30 CRANKING LEVERS FAULT
    31 LOW COOLANT TEMPERATURE
    32 DC VOLTAGE FAIL
    33 HIGH BATTERY A VOLTAGE
    34 HIGH BATTERY B VOLTAGE
    35 BATTERY A DEFECTIVE
    36 BATTERY B DEFECTIVE
    37 WATER PRESSURE SENSOR FAULT
  • 1 Device: USB connector type B Communication SAF830-D<—>PC
    2 Host: USB connector type Communication SAF830-D<—> Pendrive (external memory)
    3 Ethernet port (TCP/IP) PC monitoring: Pump and installation general condition
    4 RS 485 port (Optional) PC monitoring: Pump and installation general condition
    5 Voltage free contacts :
    up to 30 V DC / 0,5 A
    Pump running with pressure
    6 Mains failure
    7 Pump running with pressure
    8 Pump on demand
    9 Failed to start / Discharge pressure fail
    10 Not in auto mode
    11 Grouped alarms / Control fail
  • LANGUAGES / OTHER FEATURES
    1 ESPAÑOL / ENGLISH / ITALIANO / FRANÇAIS / PORTUGUES
    2 Monitored pressure switch lines: Short circuit / open circuit alarm
    3 Monitored connection solenoid box. Cranking levers fault alarm
    4 Pump demand  by pressure transducer analog reading of system pressure
    5 Current date and time (RTC with independent battery)
    6 500 last events log (starts, alarms, …)
    7 16,000 latest records of system pressure variation
    8 50 pressure / Flow pump test récords
    9 Calibration of analog measurements: Pressure / Voltage / Temperature …
    10 Digital and analog inputs and outputs checking of  on the display
    11 Accumulate engine operations hours and minutes
    12 Engine cooling circuit management
    13 Engine heating resistence management