Controllers for Electric Fire Pumps according to EN 12845 and UNE 23500
SCF830-E-U Star-delta Starting Fire Pump Controllers monitor, display and record Fire Pumps systems information. They are designed to meet and exceed the requirements of the EN 12845 and UNE 23500 standards.
SCF830-E-U controllers are high specification instruments and apply the most advanced technology in the starting and stopping process of Electric Fire Pumps. They protect the Fire Pumps through the action of the alarms both connected and generated by the controllers themselves; They manage the communication with the operator and with both the contour elements and the remote manned centre.
MAIN FEATURES: SCF830-E-U
Electric Fire Pumps Controllers: EN 12845, UNE 23500, LPC TB210, UNI 10779
Nº |
STANDARDS & TECHNICAL RULES |
1 |
Standard EN 12845 Ed.2015 +A1:Ed. 2019 |
2 |
Standard UNE 23500 Ed.2018 & Ed.2012 |
3 |
Standard UNI 10779 Ed. 2014 |
4 |
Standard IEC 61439-1 Ed. 2011 Low-voltage switchgear and controlgear assemblies |
5 |
Tech. Rule CEPREVEN R.T.1-ROC Ed.2004 |
6 |
Tech. Rule CEPREVEN R.T.2-ABA Ed.2006 |
Nº |
RANGE OF PRODUCTS (according to the type plate) |
1 |
Incoming line voltage |
600 V AC / 400 V AC / 230 V AC |
2 |
Mains frequency |
50 Hz / 60 Hz. |
3 |
Main pump motor size |
Up to 400 kW (ask for other powers) |
4 |
Jockey pump motor size |
Up to 30 kW |
5 |
Motor starter type |
DOL / λ-Δ according to the motor power / Soft starters |
Nº |
CONSTRUCTIVE FEATURES |
1 |
External enclosure |
IP65 Protected from total dust ingress (NEMA 4) |
2 |
Impact rating: IK10 (except for display) |
3 |
Fireproof grade: Fire extinguishes <30s |
4 |
Display |
Transflective: Visible under direct sunlight |
5 |
Wiring |
Halogen free |
6 |
Fireproof: RZ1 according to EN50200 (830ºC for 90min) |
7 |
Pump room temperature |
20 ºF to 122ºF (-5ºC to 55ºC) |
8 |
Isolation rating between phases |
500 Vac |
9 |
Isolation rating between phases and ground |
2.500 Vac |
10 |
Isolation impedance between phases and ground |
2 MΩ |
11 |
Earthing system |
TT system (neutral and earht connected separatelly ) |
12 |
Electromagnetic environment |
CEM-1 |
Nº |
MEASURING INSTRUMENTS IN THE DISPLAY |
1 |
System |
3 Voltmeter: voltage for every phase R-S-T (RMS) |
2 |
1 Mains frequency meter |
3 |
1 pump rotation/phase rotation |
4 |
1 Manometer pump discharge pressure ( pressure sensor required with 4-20 mA signal) |
5 |
Main pump |
1 Ammeter: pump current (RMS) |
6 |
1 active power in KW (RMS) |
7 |
1 Power factor (Cos φ) |
8 |
1 Flowmeter: (flow sender required with 4-20 mA signal) |
9 |
Jockey pump |
1 Ammeter: pump current (RMS) |
10 |
1 Active power in KW (RMS) |
11 |
1 Power factor (Cos φ) |
12 |
Controller |
1 Voltmeter: Internal voltage |
13 |
Controller |
1 Voltmeter: back-up battery voltaje |
Nº |
PUMS & SYSTEM PROTECTION |
1 |
Voltage loss |
2 |
Normal power phase reversal |
3 |
Normal frequency loss |
4 |
Main pump protection trip |
5 |
Overload main pump |
6 |
Fail to start main pump |
7 |
Jockey pump protection trip |
8 |
Controller power loss |
9 |
Low water reservoir tank |
10 |
Low priming tank level |
11 |
Battery charger failure |
12 |
No internal battery detected |
13 |
Low back-up battery voltage |
14 |
Main pump pressure switch short circuit |
15 |
Main pump pressure switch open circuit |
16 |
Low power factor main pump |
17 |
Low power factor jockey pump |
18 |
Under-current main pump |
19 |
Under-current Jockey pump |
20 |
Overload Jockey pump |
21 |
Pressure sensor fault |
22 |
Driver fault main pump |
23 |
Driver fault Jockey pump |
Nº |
COMMUNICATIONS & SIGNAL TRANSMISSION |
1 |
micro USB Port |
Boot loader for firmware upgrading |
2 |
SAF (control panel PLC ) configuration |
3 |
PC monitoring: Pump and installation general condition |
4 |
Pendrive data down-load: Events log / Pressures register log / Pump tests log |
5 |
ETHERNET |
SAF (control panel PLC ) configuration |
6 |
PC monitoring: Pump and installation general condition |
7 |
RS485 |
SAF (control panel PLC ) configuration |
8 |
PC monitoring: Pump and installation general condition |
9 |
Voltage free contacts :
up to 30 V DC / 0,3 A |
Voltage loss |
10 |
Main pump automatic mode OFF |
11 |
Fail to start / not discharge pressure |
12 |
Grouped alarmas |
13 |
Pump on demand |
14 |
Pump running with pressure |
Nº |
LANGUAGES & OTHER FEATURES |
1 |
ENGLISH / ESPAÑOL / ITALIANO / FRANÇAIS / PORTUGUES |
|
2 |
Monitored pressure switch lines: Short circuit / open circuit alarm |
|
3 |
Pump demand by pressure transducer analog reading of system pressure |
|
4 |
Jockey pump start count & working hours and minutes |
|
5 |
Main pump working hours and minutes |
|
6 |
500 last events log (starts, alarms, …) |
|
7 |
16,000 latest records of system pressure variation |
|
8 |
50 pressure / Flow pump test récords |
|
9 |
Current date and time (RTC with independent battery) |
|
10 |
Calibration of analog measurements: Pressure / Voltage / Amps … |
|
11 |
Digital and analog inputs and outputs checking of on the display |
|
12 |
80 dB buzzer |
|