FIRE FIGHTING

SCF-EM11

Diesel Fire Pump Starter

The SCF-EM11 starting switching solenoids boxes with levers (solenoids) have been designed to transmit the power of the double set of batteries, required in various specific regulations, to the auxiliary motors used to start the fire-fighting diésel engine driven pumpsets.

The activation of the solenoids installed inside can be done in any of the following two ways:

  • By electrical command coming from the SVE SCF830-D control panel.
  • By manually pressing the emergency pushbutton located on the front of the SCF-EM11 box.

    MAIN FEATURES: SCF-EM11

    Starting switching solenoids EN 12845

  • STANDARDS & TECHNICAL RULES
    1 Standard EN 12845 Ed.2016
    2 Standard UNE 23500 Ed.2018
    3 Standard UNI 10779 Ed. 2014
    4 Standard IEC 61439-1 Ed. 2011 Low-voltage switchgear and controlgear assemblies
    5 Tech. Rule CEPREVEN R.T.1-ROC Ed.2004
    6 Tech. Rule CEPREVEN R.T.2-ABA Ed.2006
  • RANGE OF MODELS
    200 Amp for 100 s 1.000 Amp. for 100 s
    12 V DC SCF-EM11-1202 SCF-EM11-1210
    24 V DC X SCF-EM11-2410
  • CONSTRUCTIVE FEATURES
    1 Enclosure Ingress protection rating: IP65
    2 Protection against impacts degree: IK10
    3 Fireproof degree: The fire is extinguished in <30s with dripping
    4 Cabling Free of halogens
    5 Fire resistance: RZ1 according to EN50200 (Max: 830º / 90min)
    6 Working temperatures From -5ºC to 50ºC