FIRE FIGHTING

SCF8C-J-AS

SCF8C-J-AS

SCF8C-J-AS. Control para bombas Jacking según la norma australiana AS 2941

SCF8C-J-AS  son instrumentos completos, de uso sencillo, automáticos y configurables, útiles para la gestión del funcionamiento de bombas Jacking hasta 7,5 kW entornos con circunstancias diversas.

Los controladores SCF8C-J-AS gobiernan el encendido y paro de la bomba Jacking y las protegen mediante la acción de diferentes alarmas, visualizan los valores e informaciones más relevantes y gestionan la comunicación tanto con los elementos de contorno como con los vigilantes remotos.

CARACTERISTICAS PRINCIPALES: SCF8C-J-AS

Control bombas Jockey mediana dimensión: AS 2941 / AS 3000

  • STANDARDS & TECHNICAL RULES
    1 Australian Standard AS 2841-13
    2 Australian Standard AS/NZS 3000:2007
  • RANGE OF MODELS (according to the type plate)
    1 Incoming line voltage 400 V AC / 230 V AC
    2 Mains frequency 50Hz / 60Hz.
    3 Jockey pump motor size Up to 7,5 kW or 2,2kW
    4 Motor starter type Direct (DOL)
  • CONSTRUCTIVE FEATURES
    1 External enclosure IP65 Protected from total dust ingress (NEMA 4)
    2 Impact rating: IK10 (except for display)
    3 Fireproof grade: Fire extinguishes <30s
    4 Display Transflective: Visible under direct sunlight
    5 Wiring Halogen free
    6 Fireproof: RZ1 according to EN50200 (830ºC for 90min)
    7 Pump room temperature 20 ºF to 122ºF (-5ºC to 55ºC)
    8 Isolation rating between phases 500 V AC
    9 Isolation rating between phases and ground 2.500 V AC
    10 Isolation impedance between phases and ground 2 MΩ
    11 Earthing system TT system (neutral and earht connected separatelly )
    12 Electromagnetic environment CEM-1
  • MEASURING INSTRUMENTS IN THE DISPLAY
    1 System 3 Voltmeter: voltage for every phase R-S-T (RMS)
    2 1 Mains frequency meter
    3 1 pump rotation/phase rotation
    4 1 Manometer pump discharge pressure ( pressure sensor required with 4-20 mA signal)
    5 Jockey pump 1 Ammeter: pump current (RMS)
    6 1 Active power in KW (RMS)
    7 1 Power factor (Cos φ)
    8 Controller 1 Voltmeter: Internal voltage
    9 Controller 1 Voltmeter: back-up battery voltage
  • PUMS & SYSTEM PROTECTION
    1 Voltage loss
    2 Normal power phase reversal
    3 Normal frequency los
    4 Jockey pump protection trip
    5 Thermal overcurrent Jockey pump
    6 Jockey pump fail to start
    7 Low water reservoir tank
    8 Fuses tripped
    9 Controller power loss
  • COMMUNICATIONS & SIGNALS TRANSMISSION
    1 USB Port Boot loader for firmware upgrading
    2 Voltage free contacts : Up to 250 V AC / 2 A Pump running
    3 Grouped alarms